Flat cylinder FF OUTSIDE (Foil Fabric coated OUTSIDE)

Flat cylinder FF OUTSIDE (Foil Fabric coated OUTSIDE)

Density
0 - 150 kg/m³
Thickness
30 - 120 mm
Length
1000
The appointment
Heating Ventilation Air ducts Conditioning Water supply Water disposal Technical equipment Power equipment Outside the premises
Functions
Vapor barrier Aesthetic appearance

The IZOTERM® FF OUTSIDE flat cylinder is a heat-insulating material ready for use (heat-insulating structure), which is made of high-quality stone wool of basalt rocks with a synthetic binder, with a cover layer of high-strength folded fabric. On the inside, the flat cylinder has trapezoidal cutouts, thanks to which the cylinder takes a given configuration on an insulated surface. All cylinders have a longitudinal overlap of foil fabric with an adhesive base and a transverse overlap to ensure sealing of the joints of the cylinders with each other. Cylinders are equipped with fittings: bends, tees

IZOTERM® FF OUTSIDE flat cylinders are designed for thermal insulation of pipelines in heating, ventilation, water supply and wastewater systems at facilities of various industries (including the food industry) and the building complex at an insulated surface temperature from minus 180 ° C to plus 550 ° C. For outdoor applications where a durable coating is required, resistant to UV radiation, environmental influences and having an aesthetic appearance.

Parameter name

Units measuring

Flat cylinder IZOTERM

RW-80 FF OUTSIDE

Flat cylinder IZOTERM

RW-100 FF OUTSIDE

Flat cylinder IZOTERM

RW-120 FF OUTSIDE

Flat cylinder IZOTERM

RW-150 FF OUTSIDE

Density

kg/m3

 from 72-90

incl.

 from 91-105

incl.

from 106-125

 incl.

from 126-150 incl.

Thermal conductivity                       Λ10

 

 

W/mK

0,035

0,036

0,037

0,038

Λ25

0,036

0,037

0,038

0,039

Λ125

0,047

0,047

0,047

0,047

Λ300

0,086

0,086

0,08

0,08

Flammability group *

Group

G1

G1

G1

G1

Operating temperature

°C

to +350

to +400

to +500

to +550

Organic matter content

%

3,5

4

4,5

4,5

Parameter name

Units measuring

Value

Length

mm

1000

Pipe Diameter (Inner Diameter)

mm

42-1420 inclusive *

Wall thickness

mm

30-120  inclusive *